PUZ-ZM35VKA
Model family: Power Inverter PUZ-ZM
1.6 kWheating capacity
1.6 kWcooling capacity
4.7SCOP
7.5SEER
Technical data
| Heating | |
|---|---|
| Economical operation temp. range, heating¹ (°C) | -20 |
| Heating capacity (kW) (min.–max.) | 1.6-5.2 |
| Rated heating capacity (kW) | 4.1 |
| SCOP (seasonal coefficient of performance) | 4.7 |
| Capacity at -15 °C | 3.12 |
| Seasonal energy efficiency class | A++ |
| Pdesign | 2.5 |
| Cooling | |
| Economical operation temp. range, cooling² (°C) | -15 |
| Cooling capacity (kW) (min.–max.) | 1.6-4.5 |
| Rated cooling capacity (kW) | 3.6 |
| SEER (seasonal energy efficiency ratio) | 7.5 |
| Seasonal energy efficiency class | A++ |
| P design | 3.6 |
| Data | |
| Dimensions (mm) H×L×W | 809x630x300 |
| Weight (kg) | 46 |
| Airflow (m³/min) heating/cooling | 45/45 |
| Noise level heating/cooling (dB(A)) | 46/46 |
| Max. operating current (A) | 13 |
| Recommended fuse (A) | 16 |
| Pipe diameter (liquid/gas) | 1/4″..1/2″ |
| Max. pipe length (m) | 50 |
| Max. height difference (m) | 30 |
| Refrigerant / charge (kg) | R32/2.0 |
¹ Su MAC-AUTO3-1.5 pašildymo kabeliu ² Su apsaugomis